During the design of a cable management system, one of the most important questions is the cable tray capacity. The capacity does not depend on size only but also on cable type, diameter, and allowable fill capacity to allow safe and efficient operation. This comprehensive guide will take you through the parameters; there are tables included for various types of cables, cable diameters, and tray sizes to help in planning.

How Many Cables Can a Cable Tray Hold

Understanding Cable Tray Capacity

Several factors determine the number of cables a cable tray can hold:

Cable Tray Size: The width and depth of the tray determine its total area.

Cable Size: The diameter of the cable affects how many can fit within the available space.

Allowable Fill Capacity: To maintain proper ventilation and allow for future maintenance, industry standards suggest filling cable trays to a maximum of 40% for data cables and 50% for power cables.

The tables below outline the estimated number of cables each tray size can accommodate, covering various types such as CAT5E, CAT6, CAT6A, CAT7, and power cables ranging from 2 sq mm to 6 sq mm.

Calculating Cable Tray Capacity

Step-by-Step Calculation Process

1.    Determine the Tray Area:

Calculate the tray area by multiplying its width by its depth. For example, a tray measuring 100 mm x 50 mm has an area of 5,000 mm².

2.    Calculate the Allowable Fill Area:

Multiply the tray area by the allowable fill capacity (40% for data cables, 50% for power cables). For a 100 mm x 50 mm tray filled with data cables, the fill area would be 5,000 mm² x 0.40 = 2,000 mm².

3.    Determine the Cross-Sectional Area of Each Cable:

The cable's cross-sectional area can be approximated using its diameter. For a circular cable, the area = Ï€ x (diameter/2)². For a CAT5E cable with a diameter of 5.5 mm, the area = 3.14 x (5.5/2)² ≈ 23.76 mm².

4.    Estimate the Number of Cables:

Divide the allowable fill area by the cross-sectional area of a single cable. For example, 2,000 mm² / 23.76 mm² ≈ 84 cables.

Cable Tray Capacity Tables for Different Cable Types

Below are the updated tables showing the number of cables that can be accommodated in various tray sizes, calculated with the above method.

1. CAT5E Cables

Cable Tray Size (mm)

Cable Diameter (mm)

Tray Area (mm²)

Allowable Fill Area (mm²)

Cross-Sectional Area per Cable (mm²)

Estimated Number of Cables

100 x 50

5.5

5,000

2,000

23.76

~84

300 x 100

5.5

30,000

12,000

23.76

~504

600 x 100

5.5

60,000

24,000

23.76

~1,009

 

2. CAT6 Cables

Cable Tray Size (mm)

Cable Diameter (mm)

Tray Area (mm²)

Allowable Fill Area (mm²)

Cross-Sectional Area per Cable (mm²)

Estimated Number of Cables

100 x 50

6.5

5,000

2,000

33.18

~60

300 x 100

6.5

30,000

12,000

33.18

~362

600 x 100

6.5

60,000

24,000

33.18

~724

 

3. CAT6A Cables

Cable Tray Size (mm)

Cable Diameter (mm)

Tray Area (mm²)

Allowable Fill Area (mm²)

Cross-Sectional Area per Cable (mm²)

Estimated Number of Cables

100 x 50

7.5

5,000

2,000

44.18

~45

300 x 100

7.5

30,000

12,000

44.18

~271

600 x 100

7.5

60,000

24,000

44.18

~542

 

4. CAT7 Cables

Cable Tray Size (mm)

Cable Diameter (mm)

Tray Area (mm²)

Allowable Fill Area (mm²)

Cross-Sectional Area per Cable (mm²)

Estimated Number of Cables

100 x 50

8.0

5,000

2,000

50.27

~40

300 x 100

8.0

30,000

12,000

50.27

~238

600 x 100

8.0

60,000

24,000

50.27

~477

 

5. Power Cables (2 sq mm to 6 sq mm)

The calculation for power cables follows a similar approach but uses a 50% fill capacity.

2 sq mm Power Cables

Cable Tray Size (mm)

Cable Diameter (mm)

Tray Area (mm²)

Allowable Fill Area (mm²)

Cross-Sectional Area per Cable (mm²)

Estimated Number of Cables

100 x 50

4.5

5,000

2,500

15.90

~157

300 x 100

4.5

30,000

15,000

15.90

~943

600 x 100

4.5

60,000

30,000

15.90

~1,887

 

3 sq mm Power Cables

Cable Tray Size (mm)

Cable Diameter (mm)

Tray Area (mm²)

Allowable Fill Area (mm²)

Cross-Sectional Area per Cable (mm²)

Estimated Number of Cables

100 x 50

5.5

5,000

2,500

23.76

~105

300 x 100

5.5

30,000

15,000

23.76

~631

600 x 100

5.5

60,000

30,000

23.76

~1,262

 

4 sq mm Power Cables

Cable Tray Size (mm)

Cable Diameter (mm)

Tray Area (mm²)

Allowable Fill Area (mm²)

Cross-Sectional Area per Cable (mm²)

Estimated Number of Cables

100 x 50

6.5

5,000

2,500

33.18

~75

300 x 100

6.5

30,000

15,000

33.18

~452

600 x 100

6.5

60,000

30,000

33.18

~904

 

6 sq mm Power Cables

Cable Tray Size (mm)

Cable Diameter (mm)

Tray Area (mm²)

Allowable Fill Area (mm²)

Cross-Sectional Area per Cable (mm²)

Estimated Number of Cables

100 x 50

8.5

5,000

2,500

56.75

~44

300 x 100

8.5

30,000

15,000

56.75

~264

600 x 100

8.5

60,000

30,000

56.75

~529

 

Frequently Asked Questions (FAQ)

1. What is the fill capacity for cable trays?

The fill capacity is the percentage of the tray area that can be occupied by cables. Industry standards typically recommend a 40% fill capacity for data cables (e.g., CAT5E, CAT6) and 50% for power cables to ensure proper ventilation and ease of maintenance.

2. How do I calculate the number of cables my tray can hold?

Calculate the tray area by multiplying the tray’s width by its depth. Then, calculate the allowable fill area (tray area x fill capacity). Finally, divide the allowable fill area by the cable's cross-sectional area.

3. Can I mix different types of cables in the same tray?

Yes, but it’s important to follow industry guidelines regarding separation and fill capacity. Mixing power and data cables might require additional spacing to reduce interference and heat buildup.

4. What happens if I exceed the fill capacity?

Exceeding the fill capacity can lead to overheating, increased electromagnetic interference, and difficulty in managing and maintaining the cables.

5. Why are there different fill capacities for data and power cables?

Data cables are more sensitive to interference and heat, so they require more space for proper ventilation. Power cables are less sensitive to these issues, allowing for a higher fill capacity.

 