TESTING OF ELECTRICAL INSTALLATION IN BUILDINGS
It is good to test the
electrical wiring of a building after the wiring is completed. Electrical
installation of buildings should satisfy at least the four tests which are
discussed further.
How to do an insulation resistance test?
Test
for insulation resistance:
This test is made with all
links in place, all lamps in position and all switches on. The insulation
resistance is measured between the earth and the whole system of the conductor or
any section thereof. The insulation resistance of the installation in megaohm
should not be less than 50 divided by the number of points in the circuit
except that it need not exceed 1 megaohm for the whole installation.
How to do a Test for resistance between the conductors?
Test
for resistance between the conductors:
When making this test, all
the switches must be on but the lamps and other loads should be removed. This
test is made between all the conductors connected to one pole (or phase
conductor of the supply) and all the conductors connected to the other pole (or
neutral phases of the supply). Leakage at cable ends is one of the common
causes of low reading so before this test, care should be taken to see that the
switches, etc. are clean. The result of the test shall not be less than the one
specified in the insulation resistance test with the load on as stated
above.
How to do the Earth continuity test?
Earth
continuity test:
The total resistance
measured from the earth electrode to any point in the earth continuity
conductor in the complete installation should not exceed one ohm.
How do Check the polarity of single pole (SP) switches?
Checking
polarity of single pole (SP) switches:
The following checks are
needed for the polarity of single pole switches:
(a)
In a two-wire installation, all non-linked single pole switches
should be checked to see whether they are all connected to the phase conductor.
(This will ensure total cut off of the current when the switch is in the off
position.) It is an important check.
(b)
If the installation is three-phase (four-wire installation),
then a test should be made to verify that every non-linked single pole switch is
fitted to a conductor connected to one of the phases and that any two of the
phases are not exposed within the specified distance of two metres. (This
ensures that there is no chance for a phase-to-phase connection.)
No comments:
Post a Comment