ELECTRICAL SUPPLY
Electrical power is
provided to the building by the Government. Electricity is distributed in small
towns and villages by overhead wires. But in large cities and towns, the
distribution is done through underground cables. The supply of electricity is
including the cables up to
1. Outer casing with coarse
sand (30 cm thick).
2. Lining with coarse
aggregate (15 cm thick).
3. Brickwork with mortar
joints.
Leaching
cesspool
the electric metre. In order to isolate the main supply
from the building, a system of fuses is installed between the supply inlet and
the electric metre board. From the fuses, the wires are led to the metre and
from there to the consumer unit. From this point, the electricity is distributed
to the various parts of the building. It is the responsibility of the owner of
the building to provide wiring and other fixtures from the metre to the
distribution board and other parts of the building (Varghese, 2012).
SINGLE AND THREE-PHASE SUPPLY
The electricity from the
sub-stations are stepped down through local transformers and supplied to nearby
buildings as a single-phase or three-phase supply (50 cycles per second at 220
volts between the phase and the neutral). Then the supply is 230 volts between
a phase and a neutral and it is 400
there shall be one
live-phase wire and a neutral. In a three-phase supply, there shall be three
live phases and a neutral.
When the electrical power load
is small and the total current drawn is less than 30 amp, a single-phase may be
sufficient. That is only for lighting and use of fans a single-phase may be
enough. However, when the load is heavy, as when the use of any type of equipment such as
air conditioners, cooling ranges, etc., it is necessary to draw current from
three live phases and a neutral. The electric current metre for a three-phase
supply is different from that of single-phase. It is a condition that all
equipment used in residences must be 220–230 volts. Instead of underground
cable, if supply is drawn from overhead insulated cable special care has to be
taken. In this case it is to be first run down the walls with insulated cables and
then turned up at the entry point of the building to prevent rainwater from running
along the cable into the electric board.
DISTRIBUTION CIRCUITS
In an ordinary building, for distribution of electricity
from the consumer control unit to other points, the supply is divided into
three separate types of circuits, viz.,
1. Lighting circuit of low capacity
2. Power circuit through ring circuit
3. Fixed appliance circuits
Red wires are used for the live wire whereas the neutral
is black or blue and earth wires are green and yellow. In the circuit, a phase
changer may also be incorporated.
MATERIALS AND DEVICES USED IN WIRING
Following
are the materials and devices used in the wiring of a building.
1. Cables
Cables consist of copper or aluminium conductors
surrounded by insulation. Aluminium conductors are used to reducing the cost but
they are inferior in quality compared to copper cables. Now-a-days stranded
wires are commonly used for better performance.
Rubber or PVC insulation may be made. In moist or wet
conditions PVC insulation may fare better than rubber.
2. Fuses
Basically, a fuse protects appliances and cables from
damage by electrical faults. The current rating of fuses should be lower than
that of the cable it has to protect. Two types of fuses are in use, viz.,
Rewirable or semi-enclosed fuses and cartridge fuses.
3. Miniature
Circuit Breaker
Now-a-days miniature circuit breakers (MCB) are used
instead of fuses. Miniature circuit breakers are single-pole switches that
automatically switches off when excess current flows. An MCB trip at 1.25
times its rated current capacity. It is only an overload device. But for the
initial cost, it has many advantages.
4. Earth
Leakage Circuit Breaker (ELCB)
An electric appliance with a fault is connected to a
line and if the metal parts are not earthed the metal may become live without
the fuse blowing. Such a situation may cause a shock to the person touching it.
On the other hand, if the metal body is earthed, then the current will flow through
the earth wire. In such a condition, it is advisable to use a tripping device called
the earth leakage circuit breaker. It automatically trips even where a small
current flows through the earth wire. This switch is connected to the neutral
line of the electric supply. When it trips, the supply to the building will be
completely cut off.
5. Residual
Current Circuit Breaker (RCCB)
This type of breaker is a much more positive protection
device that can be provided instead of an earth leakage circuit breaker to avoid
electric shocks and current leakages. An RCCB is connected to all three
phases and the neutral. It is more expensive but provides excellent protection.
WIRING OF BUILDINGS
The
following are three types of wires:
1. Sheathed wiring by surface fixing
2. Conduit installation on walls and ceilings
3. Concealed conduit wiring
Nowadays in most of the buildings concealed PVC
conduit wiring is used. The PVC conduits may be laid on the surface or
concealed. In both cases, care has to be taken to see that no water enters
the pipes. In the case of a concealed pipe, it is safe to surround the conduit in
chicken mesh reinforcement.
If you find
This information is helpful, please share it.
Thanks! For reading the article.
Electrical services include everything connected with power in a structure.
ReplyDelete